Oumefar Genset Controller Module DGS6120UC LCD Display Generator Automatic Controller Generator Set Parameters Monitoring Control Panel Automatic Engine Control Module for HGM6120UC
- ?【8 LANGUAGES AVAILABLE】: Genset Controller Module is available in 8 languages, which includes English, Chinese, Spanish, Russian, Portuguese, Turkish, Polish, French, which can be good helper to you. - ?【LCD BACKLIGHT DISPLAY】: Generator Set Controller has designed with LCD Display Panel, with backlight, and the Generator Control Panel has optional language interface and support push-button operation. - ?【AUTOMATIC SWITCHING】: Genset Controller Machine has added the function of power monitoring and power generation automatic switching control, which can bring you good using experience. - ?【EQUIPPED LOAD TSET】: Genset Controller has manufactured with load test key, and can be placed in manual test mode, in which the generation is normal, and the generator set will automatically load operation. - ?【STURDY AND DURABLE】: Genset Controller Module Shell has taken the material of plastic, which is sturdy and durable in use, with assurance, and we hope this Genset Controller Module will meet your basic need.
Product description
Features
Specification:
Item Type: Genset Controller
Material: Plastic
Mains Voltage Normal Delay: (0-3600)S
Mains Voltage Abnormal Delay: (0-3600s
Mains Voltage Low Threshold: (30-620)V
Mains Voltage High Threshold: (30 620)V
Switching Interval: (0-99.9)S
Power-On Delay: (0-3600)S
Stop Delay: (0-3600)S
Starting Times: (1-10)
Warm-Up Time: (0-300)S
Starting Time: (3-60)S
Starting Interval Time: (3-60)S
Safe Running Time: (1-60)S
Startup Idle Time: (0-3600)S
High-Speed Warm-Up Time: (0-3600)S
High Speed Cooling Time: (0-3600)S
Stop Idle Time: (0-3600)S
Power Down Time: (0-120)S
Waiting for Stop Delay: (0-120)S
Switch Closing Delay: (0-10)S
Engine Teeth: (10-300)
Abnormal Power Generation Delay: (0-20.0)S
Generating Overvoltage Shutdown Threshold: (30-620) V
Generating Undervoltage Shutdown Threshold: (30-620) V
Underspeed Shutdown Threshold: (0-6000) Rpm
Overspeed Shutdown Threshold: (0-6000) Rpm
Under Frequency Shutdown Threshold: (0-75.0) Hz
Over-Frequency Shutdown Threshold: (0-75.0) Hz
Over-Temperature Shutdown Threshold: (80-140)C
Low Oil Pressure Shutdown Adjustment Value: (0-400) Kpa
Low Fuel Level Threshold: (0-100)%
Speed Signal Loss Delay: (0-20.0)S
Failure Threshold: (0-30)V
Battery Overvoltage Threshold: (12-40)V
Battery Undervoltage Threshold: (4-30)V
Package List:
4 x Fixing Screw
1 x Instruction Manual